The device purpose
Relay Protection Testing Device DTE–450/200 (hereinafter – device) is intended for:
- adjustment and testing of simple relay protection (RPA) in place of their installation at power plants, substations, industrial plants or in the laboratory
- adjustment and testing of electroautomatics elements (electromagnetic relays, contactors, motor starters, etc.)
- adjustment and testing of circuit breakers
The device is implemented within a single enclosure, which creates additional convenience during use. It includes connecting wires and cables to connect testing devices.
Technical specifications
Power supply AC voltage | 220 V ± 10%(50Hz) |
Maximum supply consumption current, | 50 A |
Maximum power consumption | 3000 W |
Environment temperature | -10°C … +45°C |
Storage temperature | -20°C … +45°C |
Relative air humidity at + 25°C | 80% max |
Atmospheric pressure, mm Hg. | 630 – 800 |
Device weight, without connecting wires set | 30 kg max |
Continuous operation mode, at least | 120 min |
Average service time | 10 years |
Output voltage | |
Range of sinusoidal power frequency output voltage, generated by the device is divided into three subranges | 0 –– 50 V 0 –– 250 V 0 –– 450 V |
Range of rectified output voltage, generated by the device is divided into three subranges | 0 –– 50 V 0 –– 250 V 0 –– 450 V |
Output voltage measuring accuracy | 3,0 % |
Measurement resolution of the output voltage | 10 mV |
Output current | |
Range of sinusoidal power frequency output current, generated by the device is divided into two subranges | 0 –– 20 A 0 –– 200 A |
Output current measuring accuracy | 3,0 % |
Measurement resolution of the output current | 10 mA |
You can see the 3D model of the device at this link