Circuit Breaker Testing Device DTE-6M

Purpose

Circuit Breaker Testing Device DTE-6M (High-Current Circuit Breaker Test Device)

The DTE-6M Primary Injection Test Set is a modern high-current circuit breaker test device designed for verifying the performance and time–current characteristics of AC circuit breakers in the extended range of 20 A to 6000 A. This advanced equipment provides precise measurement and recording of both current and operating time of circuit breakers, including high-capacity protective devices used in industrial power systems.

Main Applications

  • Testing of low-voltage and high-capacity circuit breakers (verification of time–current characteristics up to 6 kA).
  • Primary current injection testing and certification of measuring and protective current transformers under high load.
  • Testing and calibration of overcurrent and thermal relays, including devices rated for high operating currents.
  • Fuse testing and verification for industrial power circuits.
  • Use as a controllable AC current source up to 6 kA for low-impedance laboratory and field applications.

Key Features

  • Portable and robust design – suitable for both laboratory environments and on-site high-current testing.
  • Galvanic isolation of the output circuits from the power supply ensures operator safety.
  • Extended current range – one device covers testing of circuit breakers, transformers, relays, and fuses up to 6000 A.
  • Enhanced performance compared to the DTE-3M, making it suitable for demanding industrial applications.

Price on request.
Contact us to buy the DTE-6M Primary Injection Test Set directly from the manufacturer and receive detailed information on delivery and availability.

Technical specifications

Power supply voltage*400 V ± 5%
Power supply frequency50 Hz ± 1%
Maximum no-load voltage per turn at a 400 V supply voltage2.4 V
Maximum RMS current at the output busbars6600 A
Maximum power consumption of the DTE-6M45 kVA
True RMS output current measurement and recording range: from 10% (or not less than 100 A) to 100% of the selected range, with a measurement error of less than 3%20 A – 6600 A
Output current duration measurement and recording range, with a measurement error of less than 1.5%0.01 – 99999 s
Transformer overtemperature protection threshold80 °C ± 10%
Weight of the CU-6 control unit, max.3.6 kg
Weight of the CAU-6 current amplifier unit, max.40 kg
Weight of the transport trolley, max.12 kg
Weight of one copper flexible busbar, max.3.3 kg
Weight of the CS-6 current sensor, max.2 kg
Overall dimensions of the CU-6, max.300 × 250 × 135 mm
Overall dimensions of the CAU-6, max.420 × 150 × 380 mm
Overall dimensions of the transport trolley480 × 580 × 780 mm
Average service life of the device10 years

* The device can be powered from a voltage of 230V, while the maximum output current = 4,5kA.

** Technical specifications correspond to reduced values for device operation with a single-phase voltage regulator

DTE-6M operating conditions

Environment temperature range-5°C – +35°C
Relative air humidity at +25°C≤85%.
Atmospheric pressure, mm Hg630 — 795