Purpose of the device

The DTE-450/200 Simple Protection Testing Device is designed for:
1.1. Commissioning and testing of simple relay protection devices (RPA) at their installation sites at power plants, substations, industrial facilities, or laboratories.
1.2. Commissioning and testing of electrical automation components (electromagnetic relays, contactors, starters, etc.).
1.3. Commissioning and testing of circuit breakers.

The device is housed in a single enclosure, providing added convenience during operation. It includes connection wires and cables for interfacing with the devices under test.

Technical Specifications

AC mains voltage, V230±10% (50Hz)
Maximum current consumption, A12
Maximum power consumption, (V×A)2500
Operating temperature, °C-10…+45
Storage temperature, °C-20…+45
Relative air humidity at +25 °C, %, not more than80
Atmospheric pressure, mmHgfrom 630 to 800
Device weight without connection cables, kg, not more than40
Continuous operation time, min., not less than120
Average service life, years10

Output Voltage:

Range of output sinusoidal voltage at mains frequency, generated by the device, is divided into three sub-ranges:1 –– 50 (V)
5 –– 250 (V)
7 –– 450 (V)
Range of output rectified voltage, generated by the device, is divided into three sub-ranges:1 –– 50 (V)
5 –– 250 (V)
7 –– 450 (V)
Output voltage measurement accuracy, (%)3.0
Output voltage measurement resolution, (mV)10

Output Current:

Range of output sinusoidal current at mains frequency, generated by the device, is divided into two sub-ranges:0.5 –– 20 (A)
7 –– 200 (A)
For testing external current transformers with a secondary current of 5A, the device includes a current meter range:0.1 –– 5 (A)
Output current measurement accuracy, (%)3.0
Output current measurement resolution, (mA)10

Additional:

Time interval meter range0.1 ms…99999.9 (s)
Time interval measurement accuracy, no more than0.1 (ms)
Time interval measurement resolution when working with dry contacts, ms0.1
Resolution in “BREAK” mode, ms0.1
Timer for test voltage and current application to output terminals — range10 ms…99999.9 (s)

The DTE–450/200 output parameters specification

Output Terminal U1: ~ 450/5 – Adjustable AC Voltage

Adjustment range of the output voltage, V1..505..2507..450
Rated output current, A553
Maximum output current, А885
Rated output power, kW1,5
Maximum output power, kW2,5
Adjustment step of the output voltage when using single-phase voltage regulator (laboratory autotransformer), V, at most0,10,250,45
Protection: FU1 – fuse-link, A10

Output terminal U1: ± 450/5 – Adjustable rectified voltage

Adjustment range of the output voltage, V1..505..2507..450
Rated output current, A553
Maximum output current, А885
Rated output power, kW1,5
Maximum output power, kW2,5
Adjustment step of the output voltage when using single-phase voltage regulator (laboratory autotransformer), V, at most0,10,250,45
Protection: FU1 – fuse-link, A10

Output Terminal U2: Adjustable Alternative Current and Voltage

Adjustment range of the output voltage, V0,05..10
Adjustment range of the output current, A/td>0,5…207…200
Rated output current when using single-phase voltage regulator (laboratory autotransformer), A20200
Maximum output current when using single-phase voltage regulator (laboratory autotransformer), A22220
Protection: Circuit breaker device C32, Im setting of current measurer22220

Delivery Set

№.ItemQty, pcs
1DTE-450/2000 device1 pc
2Device power cable1 pc
3Set of test cables:
3.1Flexible busbar, length – 2 m, cross-section – 25 mm22 pcs
3.2Test cable, length – 2 m, cross-section – 1.5 mm21 pc
3.3Auxiliary cable, length – 2 m1 pc
4Operation manual for DTE-450/2001
5DTE-450/200 device passport1

You can see the 3D model of the device at this link