Purpose
The DTE–70/50 diode test unit is designed for:
- testing the insulation of power high-voltage electrical cables using rectified voltage with an amplitude value up to 70 kV.
- testing solid dielectrics with sinusoidal alternating voltage of industrial frequency up to 50 kV (RMS), e.g., high-voltage components of distribution equipment;
- laboratory and research purposes.
The DTE-70/50 model is equipped with reliable analog (pointer-type) meters. This design is simple, resistant to external conditions, and capable of operating at low temperatures, where LCD indicators may become less readable. This makes the device especially suitable for use in harsh climate conditions.
We also invite you to consider the DTE-70/50D — a version of the device equipped with digital meters, or the DTE-70/50T — a new model with extended functionality.
The DTE-70/50 device is a modernized version of the AID-70/50 (AID 70 / 50) unit, designed for high-voltage testing of cable insulation and solid dielectrics. If you want to purchase a dielectric testing device directly from the manufacturer in Ukraine or find out the current price of the DTE-70/50, please contact us by email or phone provided on the website.
Technical Specifications
| Power Supply | |
|---|---|
| AC mains voltage, V | 230±10% (50…60 Hz) |
| Maximum input current, A | 10 |
| Maximum active power consumption, kVA | 2.0 |
| ⚡ Output Voltage | |
| Maximum RMS output voltage (AC), kV | 50 |
| Maximum peak output voltage (DC), kV | 70 |
| Reduced measurement error of output voltage, % | 3 |
| Output voltage indication resolution, V | 100 |
| Output Current | |
| Maximum output current (AC, up to 5 min), mA | 45 |
| Maximum output current (DC, up to 5 min), mA | 15 |
| Reduced measurement error of output current (AC/DC), % | 3 |
| Output current indication resolution, mA | 0.1 |
| Mechanical Specifications | |
| Control unit dimensions, mm | 350 × 360 × 225 |
| Control unit weight, kg | 14 |
| High-voltage unit dimensions, mm | 360 × 675 × 300 |
| High-voltage unit weight, kg | 42 |
| ⏱️ Operating Mode and Service Life | |
| Continuous operation time, not less than | 30 min |
| Average service life, years | 10 |
Delivery Package
| No. | Item | Quantity |
|---|---|---|
| 1 | Control unit (CU) | 1 |
| 2 | High-voltage unit (HVU-50) | 1 |
| 3 | Power supply cable, L = 1.75 m | 1 |
| 4 | High-voltage cable, L = 3.5 m | 1 |
| 5 | Grounding wire, L = 3.5 m | 2 |
| 6 | Fuse 5×20, 250 V, 1 A | 2 |
| 7 | Fuse 6×30, 250 V, 10 A | 2 |
| 8 | User manual | 1 |
| 9 | Passport (device certificate) | 1 |
Operating Conditions
The device is designed for operation in environments excluding exposure to aggressive external factors (rain, fog, dust, direct sunlight, and other adverse conditions) and is intended for use both as part of mobile electrical laboratories and stationary installations under the following conditions:
| Parameter | Value |
|---|---|
| Operating temperature, °С | −10…+40 |
| Storage temperature, °С | −10…+45 |
| Relative humidity at +20 °C, % | ≤ 85 |
| Atmospheric pressure, kPa | 84…106.7 (630…800 mmHg) |